Spiraling Impedance in Distance Relays - Behavior During Faults
Distance relays are indispensable in power system protection, detecting and isolating faults on transmission lines.
A noteworthy phenomenon during fault conditions is the spiraling behavior of impedance, observed on the complex plane due to the transient system response.
This article explores the mathematics behind this behavior, focusing on why the measured impedance spirals towards steady-state fault impedance. This spiraling trajectory on the complex plane is due to the transient response of the system, particularly the decaying DC component in the fault current.
DC Component: IDC(t)=−Imsin(Φ−θ)e−τ(t−tfaultl)
Source Impedance: Zs=Rs+jXs
Line Impedance (Fault Impedance): Zl=Rl+jXl
Total Fault Impedance: Ztotal=Zs+Zl=Rtotal+jXtotal
Time Constant: τ=ωRtotalXtotal
Angle of Total Fault Impedance: θ=arctan(RtotalXtotal)
Voltage at the Relay During Fault
The voltage at the relay location during the fault is: Vfaultl(t)=Vsource(t)−Ifaultl(t)Zs
Note that the DC component of current IDC(t) only causes a voltage drop across the resistive part Rs of Zs, because inductors (represented by Xs) block DC currents.
Therefore, we can write: Vfaultl(t)=Vsource(t)−IAC(t)Zs−IDC(t)Rs
Calculating the Instantaneous ImpedanceZ(t)
The instantaneous impedance seen by the relay is: Z(t)=Ifaultl(t)Vfaultl(t)=IAC(t)+IDC(t)Vsource(t)−IAC(t)Zs−IDC(t)Rs
Deriving Z(t) as a Function of Time
Introducing the Ratio k(t)
Define: k(t)=IAC(t)IDC(t)
Expressing Z(t) Using k(t)
We can rewrite the impedance equation as: Z(t)=IAC(t)(1+k(t))Vsource(t)−IAC(t)Zs−k(t)IAC(t)Rs
Simplify numerator and denominator: Z(t)=1+k(t)IAC(t)Vsource(t)−Zs−k(t)Rs
But since Vsource(t)=Vpeaksin(ωt+Φ) and IAC(t)=Imsin(ωt+Φ−θ), we can express the ratio IAC(t)Vsource(t) as:
However, since the ratio sin(ωt+Φ−θ)sin(ωt+Φ) is a function of θ and ωt+Φ, it complicates the expression. For simplification, we consider steady-state conditions where this ratio approaches a constant value.
Alternatively, recognizing that Z_total=Zs+Zl, we can write: Z(t)=1+k(t)(Zs+Zl)−Zs−k(t)Rs=1+k(t)Zl−k(t)Rs
Exponential Decay: The term e−τ(t−tfaultl) decays exponentially from its initial value at t=tfaultl.
Oscillation: The denominator sin(ωt+Φ−θ) causes k(t) to oscillate.
Therefore, k(t) is a time-varying function that decreases in magnitude over time due to the exponential decay and oscillates due to the sinusoidal denominator.
This term decreases over time as k(t) decays to zero.
Thus, the impedance can be written as:
Z(t)=Zl+ΔZ(t)
Where ΔZ(t) is a time-dependent decreasing factor that causes Z(t) to spiral towards Zl.
Demonstrating the Spiraling Behavior
Initial Conditions
At t=tfaultl:
-k(tfaultl) is at its maximum magnitude. -ΔZ(tfaultl) is significant, causing Z(tfaultl) to deviate from Zl.
Time Evolution
As t→∞:
-e−τ(t−tfaultl)→0 -k(t)→0 -ΔZ(t)→0 -Z(t)→Zl
Spiral Trajectory
The oscillatory nature of k(t) due to the sinusoidal term causes ΔZ(t) to change in both magnitude and angle over time.
The exponential decay ensures that the amplitude of ΔZ(t) decreases over time.
Combined, these effects cause Z(t) to spiral towards Zl on the complex plane.
Visualization on the Complex Plane
By plotting Z(t) over time on the complex plane:
Real Part (Re[Z(t)]) and Imaginary Part (Im[Z(t)]) vary due to ΔZ(t).
The trajectory forms a spiral that converges to the steady-state impedance Zl.
Implications for Distance Relays
Distance relays calculate impedance to determine if a fault is within their protected zone.
The spiraling impedance can cause the relay to overreach or underreach if not properly accounted for.
Protective algorithms often include filters or phasor estimation techniques to mitigate the effects of the decaying DC component.
Conclusion
The decaying DC component in the fault current causes the calculated instantaneous impedance Z(t) to change over time. The spiraling behavior of Z(t) on the complex plane is due to the combination of decreasing DC current and the oscillatory nature of the AC current. As the DC component decays, the system transitions from transient to steady-state conditions, and the calculated impedance converges to the steady-state fault impedance Zl.
Understanding this behavior is crucial for the design of distance relays, ensuring they can accurately detect and isolate faults without being misled by transient phenomena.